Calorifier Inspection, Blowdown & Descaling
Shelter Tech UK Ltd provides professional calorifier inspection, blowdown, cleaning and descaling services to maintain hot water system hygiene, efficiency and reliability.
Our experienced engineers help minimise Legionella risks, prevent sediment and scale accumulation, and support compliance with ACoP L8, HSG274 Part 2 and applicable UK water hygiene guidance.
Our Calorifier Services
We provide comprehensive calorifier inspection and maintenance services, including:
- Calorifier Inspection – Assessing internal condition, corrosion, sediment and scale accumulation.
- Calorifier Blowdown – Flushing accumulated sediment and debris from the base of calorifiers.
- Cleaning & Descaling – Removing scale, sludge and deposits to improve hygiene and heat transfer efficiency.
- Temperature Monitoring – Checking hot water flow, storage and return temperatures against recommended levels.
- Disinfection – Carrying out appropriate cleaning and disinfection where required.
- Remedial Recommendations – Identifying defects and advising on necessary repairs or improvements.
- Compliance Records – Providing inspection reports, temperature readings, maintenance records and recommendations.
Calorifier Maintenance & Compliance
Regular calorifier maintenance is essential for controlling Legionella risks and maintaining reliable hot water supplies.
HSG274 Part 2 recommends annual internal inspection and cleaning, where practicable, or periodic blowdown where internal access is unavailable. Maintenance frequency should be reviewed according to the risk assessment and inspection findings.
For systems using temperature as the primary Legionella control measure, hot water should generally be stored at 60°C or above, with circulation return temperatures maintained at 50°C or above (55°C in healthcare premises).
Routine inspections and temperature monitoring help identify potential problems before they affect water hygiene or system performance.
Improving Efficiency & Reliability
Sediment, corrosion and scale deposits can reduce heating efficiency, restrict circulation and increase operating costs.
Our maintenance services help keep calorifiers clean, improve performance, reduce breakdown risks and extend equipment life.